Abstract

In this study, we experimentally investigated the effect of heat release rate and aspect ratio of tunnel on the plug-holing phenomena in a reduced-scale model tunnel. In the view of physics, plug-holing phenomena was analyzed to develop the new modified Froude number considering the tunnel and shaft geometrics and the heat release rate of fire for natural ventilation system. As the results, plug-holing occurred when the new modified Froude number is below 2.75. Also, when the heat release rate increased or the aspect ratio decreased, the modified Froude number decreased. The new modified Froude number might have greater flexibility and be more accurate for various tunnel fire situations compared with the existing criteria to judge the occurrence of plug-holing.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.