Abstract

Safety issues are of particular importance in low-concentration gas delivery. The gas explosion propagation rule and the effects of an active powder-spraying explosion-suppression device on a gas explosion in a pipeline were experimentally studied by using an experimental system with Φ500 mm pipeline explosion suppression. The research demonstrates the gas explosion pressure and flame propagation law that were obtained in the 500-mm pipe. In combination with the action time of the active powder-spraying explosion-suppression device, its installation position in the gas transmission pipeline was determined. The active powder-spraying explosion-suppression device exhibits a clear inhibitory effect on the flame and explosion pressure of a gas explosion in the pipeline, and the inhibitory effect varies with the amount of suppressant used. Under experimental conditions, a 10-kg explosion-suppression agent can successfully suppress the explosion flame, while the explosion pressure will be greatly attenuated. The conclusions provide an important theoretical basis for effectively suppressing a gas explosion in the low-concentration gas transportation process.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.