Abstract

Gravity in multi-pass condensers affects the refrigerant flow rate distribution, owing to the gravitational pressure drop that occurs mainly in the U-bend tubes in fin and tube condensers with horizontal tubes. This effect was studied using an experimental approach. A condenser with two ‘nU’ circuits was selected, and the temperature variation of the refrigerant side was measured and compared along each circuit. The critical air velocity, which indicated the initiation of the gravity effect, was found for a given refrigerant flow rate. As the air velocity increased beyond the critical air velocity, the gravity effect (or mal-distribution of the refrigerant flow) developed further. Similarly, the critical refrigerant flow rate was also determined for a given air velocity. As the refrigerant flow rate decreased below the critical refrigerant flow rate, the gravity effect also developed further. The gravity-affected region was shown in the table with rows of air velocities and columns of refrigerant flow rates, and expressed using a single parameter for a given refrigerant flow circuit.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.