Abstract

The Kigali amendment to the Montreal Protocol has highlighted the hydrofluorocarbons (HFCs) phase out as a priority to reduce the future global mean temperature increase. R134a is the most abundant HFC in the atmosphere and therefore it must be substituted using environmentally benign alternatives. In the short term, blends of HFCs and hydrofluoroolefins can replace R134a. This paper experimentally evaluates R450A (GWP of 547), a non-flammable mixture of R1234ze(E) and R134a, in an R134a small capacity refrigeration system. The controlled experimental conditions cover evaporating temperatures from −15 to 12.5 °C and condensing temperature of 25, 30 and 35 °C (36 tests in total for each refrigerant). The experimental results showed that with only a thermostatic expansion valve adjustment the average R450A cooling capacity and COP are 9.9% and 2.9% lower than those measured using R134a. Besides, the observed compressor discharge temperature values of R450A are not greater than that of R134a.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.