Abstract
When using a variable-frequency drive at low and extra-low frequencies, it is difficult to control the current value. Standard current transformers are often used. This paper analyzes the transformer performance at frequencies below the industrial one. The objective is to study operation of the process transformer connected to an adjustable current source experimentally. The paper proves that frequency drop results in excitation current rise, core saturation, and a significant increase of the transformer current error. There are secondary current traces at various degrees of the transformer's core saturation. The authors have studied the effect of both measured current and burden resistance values experimentally on the current-measuring transformer's error within low frequency range. They give some practical advices and solutions related to the use of current transformers when measuring alternating current within the range below 50 Hz.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.