Abstract

The paper presents the results of experimental registrations and numerical simulations of the transient overvoltages caused by single phase intermittent arc earth fault in 35 kV network with isolated neutral. Experimental laboratory investigation is performed in order to implement appropriate arc fault model for arcs with low and discontinuous current. Single phase to earth arc fault is created in field in 35 kV network. Numerical model of the system is created in EMTP-ATP software. Overvoltage waveshapes and overvoltage factors are calculated and compared to measured values. Good agreement between the measured and calculated results is achieved.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.