Abstract

The present study provides experimental results of the flow pattern and thermal behavior of a none-boiling air-water two-phase flow in a helical tube with a turbulator. In order to evaluate the thermal behavior, a glass tube was put under constant heat flux. The inlet, outlet, and surface temperature of the helical tube were measured to calculate the heat transfer coefficient. The results showed that the addition of the turbulator in the helical tube leads to a rapid conversion from bubble flow to slug flow. Also, the formed bubbles are much smaller and spread radially throughout the pipe. Findings showed that the turbulator significantly improved the heat transfer of the two-phase flow, in which ratios of heat transfer enhancement with and without turbulator is 28% and 19%, respectively. Finally, cost-to-benefit ratio (C.B.R) analysis confirmed that when air-water two-phase flow transits through the helical tube are not affected by the presence or absence of turbulator.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.