Abstract

In this study six heat exchangers were experimentally investigated; three of them were aluminum foam heat exchangers and the other three were aluminum fin heat exchangers. The open cell aluminum foam heat exchangers were of PPI 10, 20, 30 features and dimensions of 200 × 200 × 100 mm. The aluminum fin heat exchangers were of the same dimensions as the open cell aluminum heat exchangers and with fin intervals of 1.6, 3.2, 4.8 mm. By using experimental data, variations of effectiveness versus velocity, pressure loss versus velocity, friction factor versus Reynolds number and Reynolds number versus Nusselt number have been investigated. The Reynolds number used in the tests was at around 5 × 10 3–9 × 10 4. It was found that, for both types of heat exchangers, as the velocity of refrigerant increases, the effectiveness drops and pressure loss increases. The effectiveness was higher at lower Reynolds numbers. It was found that aluminum fin heat exchangers transfer much more heat than their aluminum foam counter parts.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.