Abstract

Dilute dispersion of silver nano-particles in pure water was employed as the working fluid for conventional 1 mm wick-thickness sintered circular heat pipe. The nanofluid used in present study is an aqueous solution of 10 and 35 nm diameter silver nano-particles. The experiment was performed to measure the temperature distribution and compare the heat pipe temperature difference using nanofluid and DI-water. The tested nano-particle concentrations ranged from 1, 10 and 100 mg/l. The condenser section of the heat pipe was attached to a heat sink that was cooled by water supplied from a constant temperature bath maintained at 40 °C. At a same charge volume, the measured nanofluids filled heat pipe temperature distribution demonstrated that the temperature difference decreased 0.56–0.65 °C compared to DI-water at an input power of 30–50 W. In addition, the nanofluid as working medium in heat pipe can up to 70 W and is higher than pure water about 20 W.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.