Abstract

An experimental investigation is conducted to determine the effect of dimpled depth on the condensation heat transfer coefficient and pressure drop of R-134a flowing inside dimpled tubes. The test condenser is a double tube heat exchanger where the refrigerant flows inside and water flows in the annulus. The inner tube is a 1500 mm long and 8.1 mm inside diameter. The experiments are carried out for one smooth tube and three dimpled tubes having dimpled depth of 0.5, 0.75, and 1.0 mm. For each test tube, several test runs are performed over mass flux range of 300–500 kg/m2s, heat flux range of 10–20 kW/m2, and condensing temperature range of 40–50 °C. The experimental results reveal that the dimpled tube presents the significant heat transfer enhancement and pressure drop penalty. The tube with the highest dimpled depth yields the highest heat transfer enhancement and pressure drop penalty up to 83% and 892% higher than those of the smooth tube, respectively. Additionally, the overall performance of dimpled tube is evaluated in term of efficiency index. The new correlations including the effect of dimpled depth, dimpled pitch, and helical pitch on the Nusselt number and friction factor of R-134a in dimpled tube are developed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.