Abstract

The cold spray test of water spray fire extinguishing system, compressed air foam cannon fire extinguishing system and combined fire extinguishing test were carried out based on a scaled platform. The cold spray test results show that most of the water spray will be directly incorporated into the compressed air foam, and the defoaming effect of the water spray on the compressed air foam is limited. The combined fire extinguishing test shows that the water spray fire extinguishing system and the compressed air foam fire extinguishing system can achieve effective fire extinguishing under different fire extinguishing sequence conditions, and the two fire extinguishing systems can be used simultaneously in dealing with transformer oil fire. The comprehensive cooling effect of the dual system is better than that of a single system. Combining the actual characteristics and requirements of the converter station, a combination strategy of fire extinguishing system that suitable for the converter station is further proposed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.