Abstract

This work presents an experimental comparison of exergy efficiency (EE), irreversibility at the process 1–2 (evaporator exit to compressor inlet), 2–3 (compressor inlet to condenser inlet), 3–4 (condenser inlet to expansion valve inlet), 4–5 (expansion valve inlet to evaporator inlet) and 5–1 (evaporator), and coefficient of performance (COP) of R22, and its substitutes R134a, R290 and R407C in vapor compression refrigeration system (VCRS) of an air conditioner. In addition, the effects of air temperature in the freezer with reference to environment states on irreversibility and EE have been investigated. At −18°C air temperature in the freezer, 33°C reference environment state and 42% relative humidity refrigerants R22 and its substitutes R134a, R290 and R407C VCRSs the total irreversibilities are 665.7, 753.5, 582.1 and 677 W, and EEs are 22.9, 14.2, 26.5 and 20.6%, respectively. The refrigerant R290 is the best performer among candidate refrigerants but it suffers from flammability. Thus, R407C can considerably be used to replace R22.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.