Abstract

This paper investigates some exergoeconomic parameters for an underground air tunnel system based upon some operating conditions. The ratio of exergy loss rate to capital cost ( R ex) changes between 0.052 and 0.552. The total exergy losses values are obtained to be from 0.26 kW to 2.50 kW for the system. The daily average maximum cooling coefficient of performances (COP) values for the system are also obtained to be 11.96 for experimental period, while the total average COP is found to be 5.89. The overall exergy efficiency value for the system on a product/fuel basis is found to be 56.9%.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.