Abstract

The responses of an inverter-based distributed generator (IBDG) to abnormal voltage and frequency are different from those of a conventional generator because of the inverter’s operating modes. In particular, although the momentary cessation (MC) mode is essential as a control strategy in the distribution system, the MC mode can affect the power system transient stability by temporarily ceasing significant amounts of IBDG generation. To mitigate these negative effects, this study analyzed the impacts of MC capability on the power system transient stability. First, the transient stability was analyzed in relation to MC capability using the single-machine equivalent (SIME) method. A critical MC operating point (CMCOP) was then proposed to assess the severity of a transient impact and to secure the transient stability under the contingency conditions. A case study based on the Korean power system validated the feasibility and effectiveness of the proposed method.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.