Abstract

ASHRAE Guideline 36 (G36) publishes high-performance control sequences for Variable Air Volume (VAV) system operation. Retrofitting existing VAV control sequences to G36 promises to have a large potential for energy savings. However, it is difficult to estimate the savings accurately and the process of doing so can be costly and time-consuming. This paper evaluates the energy use of a multi-zone VAV system with terminal reheat using the G36 sequences and compares it to a group of baseline control sequences that represent existing practices. Spawn of EnergyPlus is used for the whole building simulation, where the envelope is modelled in EnergyPlus and the HVAC equipment and its pressure-flow network and the control sequences are modelled in Modelica. The comparison of the control sequences performance is further conducted in parametric studies. For a medium-sized commercial building, the G36 sequences provide a wide range of HVAC energy savings with an average of 31%.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.