Abstract
In order to study the relationship between the amplitude (mV) and the discharge (pC) of a typical fault of a tip discharge in a partial discharge. Therefore, three different groups of tip electrode models (tip-tip, tip-plate, tip-ball) were simulated. The relationship between magnitude and discharge volume and voltage was obtained by using amplitude detection method (Ultra High Frequency Method, Acoustic Emission Method and Transient Earth Voltage method) and Pulse Current Method respectively. Kendall correlation analysis found that the amplitude and the voltage of the AE Method in the three amplitude detection methods are closest to the variation trend of the discharge quantity and the voltage of the Pulse Current Method. Exploring the equivalence between the amplitude and the discharge of the most accurate detection means, the mathematical model with the best fit is the Sum of Sin Functions.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IOP Conference Series: Earth and Environmental Science
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.