Abstract

Analysis of heat transfer and fluid flow thermodynamic irreversibilities is realized on an example of a counter flow double pipe heat exchanger utilizing turbulent air flow as a working fluid. During the process of mathematical model creation and for different working and constructing limitations, total thermodynamic irreversibility is studied. The present work proves that the irreversibility occurred due to unequal capacity flow rates (flow imbalance irreversibility). It is concluded that the heat exchanger should be operated at effectiveness, ε, greater than 0.5 and the well operating conditions will be achieved when ε approaches one where low irreversibility is expected. A new equation is adopted to express the entropy generation numbers for imbalanced heat exchangers of similar design with smallest deviation from the exact value. The results obtained from the new equation are compared with the exact values and with those obtained by Bejan (Bejan, A., 1997, Advanced Engineering Thermodynamics, Wiley, New York).

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.