Abstract
In this work, small tracer particles, in the range 0.7–7.1 μm, were used to study deposition enhancement in a 150 mm square ventilation duct with streamwise-periodic ribs mounted on one of the principal walls, under turbulent flow condition. A new analytical technique, with very high sensitivity, was adopted to determine the spatial mass flux along the ribbed duct. On some surfaces, particle deposition enhancement as high as seven times, relative to smooth surfaces, was observed. The experimental data showed that the efficiency indexes were high for the smallest and biggest particles. Results can be used to improve the design of current filtration device for mechanical ventilation system.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.