Abstract

Due to the entry into force in 2014 of the European F-Gas Regulation n° 517/2014 and the subsequent Kigali amendment, the phase-out of the medium and high-GWP refrigerants has speeded up in all refrigeration fields. The effect on the plug-in or stand-alone systems has meant that other environmentally friendly refrigerants must replace the R134a with low or ultra-low GWP maintaining the same operating conditions and reducing the energy consumption. Extended examples of these fluids are the hydrocarbons R600a and R290 and the inorganic fluid R744 (CO2). However, there are other alternatives to the HFCs R152a and R1234yf or the hydrocarbon R1270 that have hardly been analysed and can make a positive contribution to this sector. Accordingly, this work aims to evaluate the behaviour of a commercial beverage cooler experimentally when it is optimised with six alternatives to the HFC R134a: R152a, R1234yf, R290, R1270, R600a and R744. Results demonstrated that fluids R290, R1270, R152a, R744 and R600a reduce the energy of R134a in 27.5%, 26.3%, 13.7%, 3.9% and 1.2%, respectively, while the use of R1234yf increases the energy usage to 4.1%.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.