Abstract

This paper discusses a novel methodology for determination of the efficiencies of each segment in a centralized air conditioning (A/C) plant. The methodology is useful analytical tool in energy audit where it can be used for decision support for evolution of energy conservation measures and techno-economic evaluation of the various options. The procedure is applied to three A/C plants of capacity range from 50 to 500 TR. Losses in chilled air ducts and cycling losses in the refrigerant circuit are identified to be the major causes for decrease in the efficiency and capacity under rating of the systems. Effective controls and insulation of air ducts: have been shown to be the most cost effective solutions to improve the energy efficiency of the A/C plants. The generalized experimental data on overall performance of sixteen A/C plants is also provided.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.