Abstract

Legionella pneumophila in sterile distilled water was not detected after ultraviolet irradiation by FLONLIZER, a new-type sterilizer, at a flow rate of 82.5 to 364.8 liters/hr. When irradiated by FLONLIZER at a flow rate of under 324.0 liters/hr, no viable cells of legionellae, other heterotrophic bacteria and bacterivorous protozoa were detected in the cooling tower water, which was found to contain L. pneumophila. No viable cells of L. pneumophila and L. bozemanii suspended in sterile distilled water were detected after the irradiation with UV-doses of over 6.16 X 10(3) micro W.sec/cm2. At the irradiation of low UV-doses under 1.06 X 10(4) micro W.sec/cm2, the viable count of legionellae recuperated by photoreactivation from UV-damage increased with the exposure time under a white fluorescent lamp. However, in the samples irradiated with UV-doses of over 3.52 X 10(4) micro W.sec/cm2, equal to the FLONLIZER, legionellae did not recuperate even after 18 hr illumination with a white fluorescent lamp. FLONLIZER is thus expected to act as a sterilizer which can control the legionellae inhabiting cooling tower systems placed in outdoor space.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.