Abstract
Using a triangular ice sample, AC and DC arc characteristic parameters including the constants A and n, as well as the electrode voltage drop V/sub e/ were determined under various air pressures between 45 kPa and 101 kPa. The results obtained proved that the air pressure has a substantial influence on the arc constant A and the electrode voltage drop V/sub e/. The observed decrease in the critical flashover voltage of ice-covered insulators V/sub c/ with decrease in air pressure may be explained by changing the V-I arc characteristics under these conditions.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.