Abstract The effect of wind tunnel walls on the mean pressure distributions on rough-walled circular cylinders and on cooling tower models fitted with longitudinal ribs is studied experimentally in the range of Reynolds-number independence. For circular cylinders the results are compared with analytical corrections based on formulae of Allen and Vincenti, and of Maskell, which are found to be generally applicable in this Reynolds number range. For cooling towers, a correction procedure is proposed using the base pressure coefficient, Cpb, and the dimensionless pressure rise to separation, Cpb–Cpm, where Cpm is the minimum value of the pressure coefficient. The base pressure coefficient Cpb for cooling towers is (in the Reynolds-number-independent range) a function of the boundary geometry: model shape, tunnel type (open or closed jet) and blockage, and is independent of surface roughness. The difference Cpb–Cpm, on the other hand, is mainly a function of surface roughness for both cylinders and cooling towers and is very little, if at all, affected by tunnel blockage for blockages less than, say, 15 percent.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.