Abstract

R-410A distribution was experimentally studied for a parallel flow heat exchanger having two row/four pass configuration. The heat exchanger had inlet, intermediate and row-crossing headers. Tests were conducted for the mass flux from 70 to 130kg/m2s with inlet quality 0.2 and exit superheat 5°C. The insert hole size was varied from 2.0mm to 6.0mm. Results showed that the optimum insert hole diameter was 4.0mm. At the hole diameter, thermal degradation was 0.4–5.1%, which increased as mass flux decreased. Flow distribution at the inlet header generally followed the well-known trend. More liquid flowed into downstream channels as mass flux increased. At the intermediate headers, more liquid was supplied into upstream channels. The flow distribution at the front row was not dependent on the insert hole size. On the other hand, the flow distribution at the rear row was heavily dependent on the insert hole size.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.