Abstract

The purpose of the present study was to investigate the effect of electronic anti-fouling (EAF) technology on fouling mitigation in a heat exchanger in an open cooling-tower system. Two tests were performed in a rectangular heat-transfer channel at 5 cycles of concentration: one without the EAF treatment and the other with the EAF treatment. The fouling resistance in the case with the EAF treatment was about 70% less than that in the case without the EAF treatment at the end of 270-hr tests.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.