Abstract

The effect of discharge cooling using condensate water from the evaporator on the performance of an air conditioner has been experimentally investigated. Instead of laboratory testing, the air conditioner was tested under real conditions, as is generally an AC unit installed in a room. The indoor unit was installed inside the room at a height of 2.6 m from the floor, while the outdoor unit was installed outside at floor level. In this research, the air conditioner was tested under two conditions, i.e., normal condition without discharge cooling and modified condition in which the condensate from the evaporator was flown and dripped to the discharge pipe. The use of discharge cooling could decrease suction and discharge pressure, as well as suction and discharge temperature. It also slightly decreases supply air temperature. Better performance of the air conditioner with the use of discharge cooling was shown by the decrease of power consumption by 3.5% and increase of cooling capacity by 2.45%. As a result, the coefficient of performance (COP) increases by 6.31%.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.