Abstract

The objective of paper is to analyze the performance of the Vapour Compression Refrigeration (VCR) system by change the profile of condenser coil and with sub cooling system. An experiment is conducted on VCR system with different condenser profiles and also with sub cooling system at steady state evaporator temperature and calculated mass flow rate of refrigerant, refrigeration effect, works done and COP. From results of experiment, Refrigeration Effect in case of helical coiled condenser is increased by 3 kJ compared to straight coiled condenser and Refrigeration Effect in case of helical coiled condenser with sub-cooling is increased by 15.3% compared to helical coiled condenser without sub-cooling. COP in case of helical coiled condenser is increased by 20% compared to straight coiled condenser and COP in case of helical coiled condenser with sub-cooling is increased by 9.7% compared to helical coiled condenser without sub-cooling.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.