Abstract

This paper presents a dynamic model to compute the DC flashover voltage for a fixed washed high voltage insulator. This model provides a combination between the static flashover and dynamic arc models. The proposed model takes the pollution layer resistance variation with time during washing into consideration. This variation is experimentally measured at different equivalent salt deposit density (ESDD) values. A mathematical equation for computing the pollution resistance variation with time during washing process is proposed. The DC flashover voltage is computed using the proposed flashover model at different pollution levels. The proposed flashover model is experimentally validated considering the adopted ESDD values. Also, the obtained results show a good agreement between the proposed model and experimental results. The effect of washing water flow rate on flashover voltage is preliminary investigated. Finally, the present study improves fixed washing systems and decreases the flashover during the washing process.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.