This paper proposes a new control method of three-phase active power filters for reducing the dc capacitor voltage fluctuations in transient load change. The proposed control method introduces a new $\boldsymbol{k}$ -step compensator, which maintains the mean active power flowing into the dc capacitor at zero every $\boldsymbol{1/(k-1)}$ ac line period. Therefore, the compensator can suppress the transient voltage fluctuations across the dc capacitor even when a quick load change occurs. This paper theoretically reveals the relationship between the step number $\boldsymbol{k}$ and the reduction effect of the dc voltage fluctuations. The experimental setup introducing the proposed seven-step compensator exhibits a good suppression effect of the dc voltage fluctuations and makes it possible to reduce the required capacitance value of the dc capacitor by a factor of seven.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.