Abstract
This paper provides a comparative study of coordinated voltage control (CVC) strategies for on-load tap-changers (OLTCs) and voltage regulator (VRs) under active and passive network management schemes (ANM and PNM). In PNM scheme, OLTC and VR are restricted to only regulate the secondary bus voltages at fixed set-points, while in ANM scheme, control of the secondary bus voltages within the statutory voltage range is allowed, thus providing area-based voltage controls. In this paper, the dynamic model of a 33kV 16-bus United Kingdom generic distribution system (UKGDS) is firstly implemented in PSCAD/EMTDC and validated with a steady-state model, using optimal power flow (OPF)-based technique, developed in GAMS software. Secondly, the OLTC and VR controls under ANM and PNM schemes are developed with discrete tap-changers, and tested considering different load profiles and dynamic loads. The results show that the ANM scheme allows considerable utilization of OLTC and VR compared to PNM scheme, but also may increase the loading of these devices depending on load levels and voltage profile in the power network.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.