Abstract

Reduction of data centre power consumption is a timely challenge. Waste heat reuse is another focus area when developing energy efficient and sustainable data centres. And these two issues are interconnected through liquid cooling of server racks and/or direct-to-chip liquid cooling. Both of these solutions make it possible to transfer a significant proportion of the waste heat energy back to profitable use. Nevertheless, the heat reusing opportunity is not the only benefit direct-to-chip liquid cooling may offer. Another benefit is the notable reduction of power consumption related to cooling fans associated with server blades and rack-level cooling systems. To evaluate this benefit, we performed power consumption and performance measurements in a subarctic supercomputer centre hosting a cluster of 632 blade nodes. Our study concentrated on a 47-node subset that we analysed when the servers were executing the LINPACK benchmark. Our conclusion is that direct-to-chip liquid cooling can reduce the total power consumption, in this case, up to 14.4% depending on the inlet air temperature.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.