Abstract

Modern underground coal mines can be very large, having a total connected load in excess of 15,000 hp. These mines generally have many miles of high-power conveyor belts and IS or more miles of high-voltage power cables at distribution voltages of 12.47, 13.2, 13.8, or 14.4 kV. The shielded cables used in mine power distribution systems have a significant level of capacitance, on the order of 110 pF per ft. This level of capacitance, in an extensive power distribution system at today's voltage levels, can cause significant charging currents during a ground fault. This paper addresses the potential detrimental effects of capacitance charging currents during line-to-ground faults in mine power distribution systems. A representative mine power system is modeled and simulations with faults at various locations are conducted to evaluate the effects of this capacitance on the level of fault current and relay selectivity. The paper also includes results of capacitance measurements made on mine power feeder cables used to validate the simulation model.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.