Abstract

Abstract The vulnerability of electrical cables exposed to a fire environment is of particular concern to the nuclear power plant community. The community is interested in data that could be used for predicting cable failures during a fire situation. For this reason, a cable test program was conducted using two different types of cable insulation. Several different exposure heat fluxes were tested, as well as different test arrangements such as cable trays and conduits. The program revealed that a single failure temperature for all cable types is not recommended, but if it is necessary a reasonable temperature could be chosen for the thermosets tested in this project.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.