Abstract

This paper considers stealthy cyber-physical attacks in power systems where one or more lines and buses are disconnected by opening their respective switches/circuit breakers and to conceal such attacks, the SCADA and PMU measurements are manipulated stealthily. The paper presents a framework based on the non-linear power flow model to characterize such cyber-physical attacks and proposes a technique that uses switching transients for detecting them. The detection methodology uses the fact that any physical disconnection will cause a notable amount of transients in the system. These transient components measured by the PMUs are used to validate the legitimacy of the steady-state values of SCADA and PMU measurements and detect stealthy line disconnection and bus outage attacks. The proposed technique has been tested on the IEEE 30 bus system and it is shown that it can detect the cyber-physical attacks that conceal multiple line disconnections and bus outages under various load conditions.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.