Abstract

Low voltage dc distribution grids face issues associated with arc faults, aggravated by the absence of current zero crossing. The focus of this paper is to comprehensively develop a method of series arc fault detection at the load side power electronics, based on the electrode dependent initial voltage drop occurring at the arc initiation. The proposed arc detection algorithm is described along with the structure and time constants of the designed bandpass filter. The operational boundaries of the arc detection algorithm are defined for copper electrodes depending on the set threshold voltage and the system parameters, like grid inductance, resistance, and the load capacitance. Further, the detection time and the zone of guaranteed positive detection are depicted. These are validated through test simulations on the state space model of the system. Finally, experimental validation of the proposed scheme is carried out, wherein, a series arc is generated in the dc circuit and the programmed micro-controller provides a real time signal upon detecting the arcing event. The results on variation in detection time with set threshold voltage are also presented experimentally.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.