Abstract
We have studied a DC circuit breaker with an HTS fault current limiting (FCL) module for MVDC(Medium-Voltage Direct Current) power grid. The attached FCL module can reduce the burden of the circuit breaker to make the system break the fault current faster as well as safer. In this paper, we will present the design of an HTS fault current limiting module with 2G REBCO conductor for the MVDC power grid with the rated voltage of 15 kV. Among several different type of 2G REBCO conductor from different suppliers, we selected the most suitable conductor, which was SuNAM's stabilizer free REBCO conductor, based on the overcurrent test results. And we performed the circuit simulation to verify the module's validity for rated current of 3 kA in 15 kV class DC grid.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.