Abstract

This paper presents a new single-pole switching scheme for depressing turbine–generator blade torsional torque. Since the single-phase fault occurs more frequently in power line accidents, there are many advantages on stability and reliability by using single-pole switching on the faulty phase. Nevertheless, the two healthy phases still maintain power transmission during the dead time between single-pole tripping and line reclosing, which induce significantly negative-sequence current flowing into the nearby turbine–generator. This would cause super-synchronous resonance (SPSR) effect on low-pressure (LP) turbine blades and even result in fatigue damage. The short-time compensation of a grounding capacitor set up at the neutral of the wye transformer is proposed to eliminate this negative-sequence current. Then the induced adverse effect on blades can be precluded.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.