Abstract

The automated distribution system using distribution line carrier (DLC) needs a two way communication between the various controlled terminals and the main substation. Digital data should be transmitted over the distribution power lines from the main substation to the transceivers in the distribution system and vice versa. The distribution system is a hostile medium for data transmission [i.e., high noise levels and standing wave patterns with low voltage nodes (as a result of signal reflections in the system)]. This hostility leads to low signal-to-noise ratio (SNR) locations and subsequently to high probability of bit error at these locations. The bus impedance matrix was developed for medium voltage distribution system. An actual medium voltage distribution line was tested. The actual measurements of the tested line verified the validity of the derived equations. The above mentioned line with the addition of a branch is used as an example in this paper. This paper derives (SNR) probability of bit error and performance measure transfer rate of information bits (TRIB) matrices of any DLC system starting from the bus impedance matrix.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.