Abstract

Fast isolation and detection of DC faults is currently a limiting factor in high power DC transmission grid development. Recent research has shown that the role of DC/DC converters is becoming increasingly important in solving various DC grid challenges such as voltage stepping, galvanic isolation and power regulation. This paper focuses on an additional important feature of bidirectional dual active bridge (DAB) DC-DC converters which make it attractive for future DC grids; it's inherent fault isolation capability which does not need control intervention to limit fault current in case of the most severe DC faults. Detailed analytical, simulation and experimental study are performed by subjecting the converter to DC short circuit faults at its DC voltage terminals. The results obtained have shown significant advantage of DAB where fault current is less than rated current during the fault duration. Thus no control action is necessary from the non-faulted bridge to limit fault current and no external DC circuit breakers are required. This advantage makes DAB converter feasible for DC grid integration.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.