Abstract

A dc arc flash hazard exists in solar photovoltaic (PV) power systems, but there is no widely accepted methodology for characterizing the severity of the hazard. Calculation methods have been proposed, and most rely on the nameplate $I$ – $V$ characteristic of the PV modules at standard test conditions to determine the worst case incident energy. This paper proposes to consider other factors in performing a dc arc flash hazard analysis, including possible weather conditions and variations of PV module characteristics from the datasheet ratings. It is recommended to consider two conditions when determining the worst case incident energy from a PV system: 1) the failure of all protective devices to trip within 2 s due to insufficient current and 2) the array output power exceeding the nameplate rating due to technological and environmental factors.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.