Abstract

The design of transmission systems requires electric field distribution estimation, which, in case of HVDC application is strongly sensitive to thermal and electrical configuration as well as to the nature of dielectric materials being used owing to the resistive field distribution. In this paper, the field distribution in a dielectric bilayer of XLPE and rubber materials, as representative of cable junctions, is estimated based on experimental data on field and temperature dependencies of conductivity. Through space charge measurements on bi-layer dielectrics, it is shown that the space charge density and electric field distributions are to a first order estimation consistent with data issued from conductivity measurements. Most notably, the interface charge building up between the two dielectrics changes sign, depending on field and temperature. However, in the high field range (order of 20 kV/mm), charge build-up in the bulk of dielectric materials introduces further distortion to field distribution.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.