Abstract
This work is concerned with the control strategy for the parallel operation of distributed generation systems (DGS) in a standalone ac power supply. The proposed control method uses only low-bandwidth data communication signals between each generation system in addition to the locally measurable feedback signals. This is achieved by combining two control methods: droop control method and average power control method. The average power method with slow update rate is used in order to overcome the sensitivity about voltage and current measurement errors. In addition, a harmonic droop scheme for sharing harmonic content of the load currents is proposed based on the voltages and currents control algorithm. Experimental and simulation studies using two parallel three-phase pulsewidth modulation (PWM) inverters are presented to show the effectiveness of the proposed control.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.