Abstract

Local heat transfer and pressure drop measurements were made during condensation of CFC11 in horizontal microfin tubes. A smooth tube and two microfin tubes with different fin dimensions were tested. Flow observation study with use of an industrial borescope revealed that the condensate flowed along the grooves, and a thick condensate film covered fins in the lower part of the tube in the low quality region. Static pressure gradients in the microfin tubes were up to 70% larger than that in the smooth tube. A correlation equation for the local frictional pressure gradient was derived, in which the effect of refrigerant mass velocity was introduced on the basis of the flow regime consideration. The measured frictional pressure gradient data were found by the present method to have a mean absolute deviation of 8.3%.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.