Abstract

Traditionally short-circuit protection operation time delays in medium-voltage (MV) networks have been dependent on magnitude of fault-current or impedance with fixed time delays or inverse time curves without consideration of protection selectivity issues with distributed generation (DG) units’ low-voltage-ride-through (LVRT) curves and possibility of intended island operation. In the future, these issues need to be considered increasingly in MV network protection specifications. In this paper two new future-proof directional short-circuit protection schemes are compared and evaluated. Both schemes enable, without use of high-speed communication, the definition of grid code LVRT curve compatible voltage dependent protection operation time delays during grid connected operation for intelligent electronic devices (IEDs) in MV distribution network which consists of multiple protection zones.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.