Abstract

In response to a batch of composite insulator temperature rise of a 500kV transmission line, field infrared test were conducted and 17 typical composite insulator with temperature rise were tested in laboratory. The temperature rise value with test time were grasped and internal defect were confirmed by anatomy. Comparing the results of laboratory and field test, the on-site tower test defect judgement accuracy were obtained. It is indicated that the on-site tower test defect judgement accuracy based on V string composite insulator with temperature rise is 46.15%. The temperature rise of poor adhesion and initial stage decay in laboratory could be little. The temperature rise of rod with internal defect stay increasing within the 30 min laboratory test time. It is recommended that the laboratory infrared test accuracy could be promoted by increasing applied voltage time and concerning rod temperature change curve. For field infrared test, the test method combined with drone to reduce the obstruction of insulator rod, and with rod temperature distribution characteristic to reduce the interference of visible light is recommend.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.