Abstract

A comparative energetic evaluation of R1234yf, R1234ze(E) and R450A as alternatives to R134a in a variable speed compressor is carried out. A compressor model based on dimensionless numbers was obtained using the Buckingham π-theorem, which was validated with experimental data; showing that the prediction error of the model is lower than ±10% and ±2 K for temperature. The experimental data were obtained by testing R134a, R1234yf, R1234ze(E) and R450A for a wide range of operating conditions. Results obtained with the validated model, show that the dimensionless approach provides a similar estimation of energy parameters compared with the experimental results, such as power consumption, refrigerant mass flow rate, cooling capacity, COP, discharge temperature and compressor efficiencies for each refrigerant tested using the dimensionless approach proposed. The comparative evaluation of the compressor predictions shows a reduction in the cooling capacity obtained with R1234yf, R450A and R1234ze(E), in comparison with R134a. Also, COP values for R1234yf, R450A, and R1234ze(E) are lower than those obtained from R134a. Finally, results shows that the dimensionless correlation compressor model can be used to predict the performance of other reciprocating compressors, at similar operating conditions for a wide range of compressor rotation speed, with a reasonable accuracy.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.