Abstract

Crimped and mechanically bolted aluminum and copper connectors are commonly used for terminating industrial electrical power cables with ratings up to 600 V. Aluminum connectors are available for use with aluminum or copper conductor, and copper connectors are available for use with copper conductor only. The performance of copper and aluminum connectors was compared by conducting accelerated aging under corrosive environmental conditions. The testing consisted of 2000 hours of cyclic salt fog environmental exposure, in conjunction with periodic electrical current burst testing. The connectors were evaluated by comparing the change in resistance of the test samples as the test progressed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.