Abstract
The 4th generation of district heating systems face a potential problem where lowered water temperatures lead to higher flow rates, which requires higher hydraulic capacity in terms of pipe and pump sizes. This increases the effect of the already existing issue of hydraulic bottlenecks, causing peripheral units (customers) to experience reduced flow rates. A coordinating control strategy is presented in this work aimed at reducing the effect of such bottlenecks on the comfort of customers. This is done by distributing the flow deficit over many units rather than a few. Previous works mainly focus on MPC-structured controllers that depend on complex system models and online optimization techniques. This work proposes a method that requires little information about models for individual units and minimal IT communication between control systems. The proposed method is compared with a traditional control strategy and an optimal baseline in a simulation study. This shows that the proposed method can decrease the worst case indoor temperature deviations.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.