Abstract
The hydraulic, radial force fluctuation acting on the runner of a Francis-type pump-turbine was investigated experimentally. Five model pump-turbines of different specific speeds were tested. In pumping operation, the amplitude of the fluctuation increases as discharge decreases. In generating operation, the maximum amplitude appears with the draft surge frequency during partial load operation. The runner speed frequency component always appears. Components with 0.5 to 1.0 times the runner speed frequency become dominant when maximum amplitude fluctuation occurs during transient operations.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.