Abstract

This paper aims at developing an analytical model for the coupled heat and mass transfer processes in a counterflow Reversibly Used Cooling Tower (RUCT) based on operating conditions, which is more realistic than most conventionally adopted Merkel approximations. Temperature and moisture content differences are chosen as the driving forces of heat and mass transfer correspondingly and a system of specific difference equations is developed to solve the model more efficiently. The model is investigated by using an iterative algorithm, which is validated with the experimental data reported. The analytical model also accommodates the direct and quick calculation of air and water temperature profiles, moisture content of air and the water mass flow rate change along the vertical length of the RUCT. With the aid of the developed model, the thermal behavior of the counterflow RUCT under various operating and environmental conditions is also studied in this paper. The results reveal that the proposed model can provide a theoretical foundation for practical design and performance evaluation of counterflow RUCT.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.